CTS CHILLED TowerW Series

This system, used to cool semiconductor-production equipment, is compared below with the chilled tower, air-cooled chiller, turbo-refrigeration and gas-combustion cold water generation systems, in terms of power requirement, annual power consumption and annual running costs.

< Product Lineup >
Heat needed for cooling purposes 279kW (240,000kcal/h)
Water volume 48m3/h  (800 l/min)
Water temperature at inlet 25°C
Water temperature at outlet 20°C
Operating time 24 hours, 365 days
Meteorological conditions Those of Kanto region
Electricity rates 10 yen/kW・h
Basic electricity rates 1,550 yen/kW・Month
Water rates Clean water 200 yen/m3
Sewage water 190 yen/m3
Gas rates 44 yen/Nm3  (11,000kcal/Nm3)

Below are diagrammatic overviews of each system (figures 1-5).

Figure 1: Chilled tower system
Chilled tower(TM)(air-cooled type)
Figure 2: Air-cooled chiller system
Chilled tower(TM)(air-cooled type)
Figure 3: Water-cooled chilling system
Chilled tower(TM)(air-cooled type)
Figure 4: Turbo-refrigeration system (As this system is used in tandem with air-conditioning loads, the figures below reflect only 22% of actual levels.)
Chilled tower(TM)(air-cooled type)
Figure 5: Cold water generation system (As this system is used in tandem with air-conditioning loads, the figures below reflect only 22% of actual levels.)
Chilled tower(TM)(air-cooled type)
Chart 1: Estimated power requirement, annual power consumption and annual running costs
Unit Chilled tower Air-cooled chiller Water- cooled chiller Turbo-refrigerated
system
Cold-water generation system
Power requirement kW 82.7 128.9 100.1 98.9 35.5
Annual power
consumption
kW・h 237,396 830,200 697,946 712,693 310,104
Annual gas
consumption
Nm3 0 0 0 0 156,876
Water consumption m3 4,974 0 5,735 5,662 8,777
Annual electricity rates ¥ 2,374,000 8,302,000 6,979,000 7,127,000 3,101,000
Basic electricity rates ¥ 1,538,000 2,398,000 1,862,000 1,840,000 660,000
Gas rates ¥ 0 0 0 0 6,903,000
Annual water rates ¥ 1,229,000 0 1,417,000 1,399,000 2,169,000
Annual running costs ¥ 5,141,000 10,700,000 10,258,000 10,366,000 12,833,000

In comparison with other systems, the chilled tower system offers savings of 16% ~ 35% in terms of power requirement (excluding the cold-water generation system).

With regard to annual running costs, the system saves

  • approximately ¥5.5 million (approximately 52%) compared with the air-cooled chilling system
  • approximately ¥5.1 million (approximately 50%), compared with the water-cooled chilling system
  • approximately ¥5.2 million (approximately 50%), compared with the turbo-refrigeratied system
  • approximately ¥7.6 million (approximately 60%), compared with the cold-water generaton system

proving that it has major merits of economy.